FX2N-48ER

  • Manufacturer : Mitsubishi Electric

  • Product No.: FX2N-48ER

  • Product type: I / O Expansion Unit 

  • Application sequencer : FX1N, FX3G, FX2N, FX3U

  • Rated voltage : AC 100 V to 240 V

  • Voltage tolerance range : AC 85V ~ 264V

  • Rated frequency : 50/60 Hz

  • Power supply fuse : 250 V 5 A

  • Inrush current : AC 100 V: maximum 40 A 5 ms or less AC 200 V: maximum 60 A 5 ms or less

  • power consumption : 35W

  • 24 VDC service power supply : 24 VDC 460 mA or less When connecting input / output extension block, 24 VDC service power is consumed.

  • Input specification :

  • Number of input points : 24 points

  • Input connection shape : Removable terminal block (M3 screw)

  • Input format : sink

  • Input signal voltage : DC 24 V ± 10%

  • Input impedance : 4.3 kO

  • Input signal current : 5 mA / 24 VDC

  • Input ON sensitivity current : 3.5 mA or more

  • Input OFF sensitivity current : 1.5 mA or less

  • Input response time : About 10 ms

  • Input signal format : No-voltage contact input or NPN open collector transistor

  • Input circuit insulation : Photocoupler insulation

  • Input operation display : LED on the panel when input is ON

  • Number of output points : 24 points

  • Output connection shape : Removable terminal block (M3 screw)

  • Output type / format : relay

  • External power supply : AC 250 V DC 30 V or less

  • Maximum load Resistive load : Please set the total load current per 2A / 1 point common as follows. . Output 4 points / common: 8 A or less . Output 8 points / common: 8 A or less

  • Inductive load : 80VA

  • Minimum load : DC 5 V 2 mA (reference value)

  • Response time OFF ? ON : About 10 ms

  • ON ? OFF : About 10 ms

  • Circuit insulation : Mechanical insulation

  • Output operation indication : When the relay coil is energized LED on the panel is lit

  • Ambient temperature : 0 to 55 ° C. ... Operating -25 to 75 ° C. ..... Save

  • Relative humidity : 5 to 95% RH (noncondensing).... in operation

  • Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2

  • Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 Ten times in each of X, Y, Z directions (80 minutes in total in total) The criterion is based on IEC 61131-2

  • Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2

  • Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2

  • Impact resistance : 147 m / s 2 , working time 11 ms, criterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2

  • Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 µs, rising 1 ns, with noise si

  • tor with period of 30 to 100 Hz

  • Withstand voltage : Between the power supply terminal (AC power supply) and the earth terminal: AC 1500 V for 1 minute 24 VDC Service power supply and between the input terminal (24 VDC) and the earth terminal: 500 V AC for 1 minute Between the output terminal (relay)

  • Insulation resistance : Between each terminal and earth terminal: 500 MV DC 500 MO or more with an insulation resistance meter

  • ground : Class D grounding (grounding resistance: 100 O or less)Grounding should be dedicated ground or common ground.

  • Use atmosphere : There is no corrosive property, flammable gas, conductive dust (dust) is not serious

  • Use altitude : Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.